UPS GeTX Online GXK-1-1-3-CO, 3KV (3000VA) HF LCD battery 12-9 *6

(0 Reviews)

Brand: GETX

IQD 550,000

In Stock
1

Specification

Model: GXK-1-1-3-CO

Capacity: 3000VA / 2700W

Key Features:

  • High power density
  • Online double conversion with full digital control
  • Wide input voltage range (110–300Vac)
  • Input power factor: 0.99 with PFC
  • Selectable output voltage: 208/220/230/240Vac
  • Smart charger design for optimized battery performance
  • Maximum charging current expandable to 12A (long-run unit)
  • Emergency Power Off (EPO) function
  • Versatile LCD human-computer interface
  • ECO mode for energy saving
  • Multiple communication interfaces: RS232 (USB/EPO/Relay/SNMP card optional)

Input:

Nominal Voltage: 208/220/230/240Vac

Input Voltage Range: 110–300Vac (176–280Vac @ 100% load)

Input Frequency Range: 40–70Hz (auto-sensing)

Input Power Factor: ≥0.99

Output:

Output Voltage: 208/220/230/240Vac

Voltage Regulation: ±1%

Power Factor: 0.9

Output Frequency:

  • Line Mode: 46–54Hz or 56–64Hz
  • Battery Mode: 50/60Hz ±0.1Hz
  • Crest Factor: 3:1
  • Harmonic Distortion:
  • ≤3% Linear Load
  • ≤5% Nonlinear Load
  • Transfer Time:
  • AC to Battery: 0ms
  • Inverter to Bypass: 4ms (Typical)
  • Output Waveform: Pure Sinewave

Efficiency:

AC Mode: 91%

Battery Mode: 88%

Battery:

Number of Batteries: 6

Capacity: 12V / 9Ah

Recharge Time: 4 hours to 90%

Charging Voltage: 82.2Vdc ±1%

Max Charging Current: 1A

Indicators:

LED Display: Line mode, Battery mode, ECO mode, Bypass mode, Battery low voltage, Overload, UPS fault

LCD Display: Input voltage, frequency, output voltage, output frequency, load %, battery voltage, inner temperature, backup time

Alarm:

Battery Mode: Beeping every 4 seconds

Battery Low: Beeping every second

Overload: Beeping twice every second

Fault: Continuous beeping

Physical:

Dimensions (W × D × H): 191 × 460 × 337 mm

Net Weight: 24.5 kg

Environment:

Operating Temperature: 0–40°C

Storage Temperature: -25–55°C

Humidity: 20–95% RH (non-condensing)

Altitude: <1500m (derating required >1500m)

Noise Level: <50dB @ 1 meter

Standards:

Safety: IEC/EN62040-1, IEC/EN62477-1

EMC: IEC/EN62040-2, IEC61000-4-2/3/4/5/6, IEC61000-4-8